Analog Input

AI 023

Analog Input

  • 2 analog resistance or temperature inputs (16 bits)
  • 5 resistance measuring ranges from 0-5000 Ω
  • Supported temperature sensors: PT100/PT1000/NI100/NI1000/diverse KTY
  • Sensor connection with 2 or 4-wire measuring technology possible

 

For the S-DIAS system, EPLAN Macros are available for simple integration into the control cabinet.

Analog Inputs

Type

Resistance

Number

2

Resolution

16 bits

Sensor types

1: 0 ... 250 Ω

2: 0 ... 500 Ω

3: 0 ... 1000 Ω

4: 0 ... 2500 Ω

5: 0 ... 5000 Ω

Measurement range

0 ... 5000 Ω

Measurement precision

±0.3 % of maximum measurement value

Conversion time for all channels

4 ms

Hardware filter

10 kHz, low pass 2nd order

Software filter

configurable

Galvanic isolation

Yes

Analog Inputs

Type

temperature

Number

2

Resolution

16 bits

Sensor types

PT100

PT1000

NI100

NI1000

div. KTY

Measurement range

-200 ... +850 °C or 18.5-4575.3 Ω

Measurement precision

±0.3 % of maximum measurement value

Conversion time for all channels

4 ms

Hardware filter

10 kHz, low pass 2nd order

Software filter

configurable

Galvanic isolation

Yes

Mechanical Features

Dimensions

12.5 x 104 x 72 mm (W x H x D)

Protection type

IP20

Article Number/Certification

Article number

20-009-023

Standardization/­certification

designed according to UL

pdf | 139 KB
Product sheet AI 023
zip | 451 KB
STEP File AI 023
Contact

We look forward to your inquiry!

Tell us your concerns and we will contact you as soon as possible.