For the S-DIAS system, EPLAN Macros are available for simple integration into the control cabinet.
Analog Inputs |
|
Type |
±10 V DC resp. potentiometer 0-100 % |
Number |
4 |
Resolution |
16 bits |
Measurement range |
-10 V ... +10 V or 0 ... 100 % (potentiometer) |
Measurement precision |
±0.3 % of maximum measurement value or ±0.35 % of the maximum value |
Conversion time for all channels |
Speed mode: 200 µs |
Cable break monitor |
Yes |
Hardware filter |
typically 1 kHz, low pass 3rd order |
Software filter |
configurable, low pass 1st order |
Analog Outputs |
|
Type |
standard |
Number |
4 |
Output range |
-10 V ... +10 V |
Resolution |
12 bits |
Refresh time for all channels |
≥ 500 μs (corresponds to the S-DIAS cyclic time) |
Output voltage capacity |
> 5 kΩ |
Settling time |
50 µs (63 % of the end value) 100 µs (86 % of the end value) 250 µs (99 % of the end value) |
Accuracy |
±0.5 % of maximum output value |
Reference Output |
|
Number |
1 |
Reference voltage |
+10 V DC |
Allowable output current |
maximum 10 mA (< HW version 3.5), maximum 16.7 mA (≥ HW version 3.5) |
Short-circuit proof, current limited |
Yes |
Accuracy |
±0.5 % |
Mechanical Features |
|
Dimensions |
12.5 x 104 x 72 mm (W x H x D) |
Protection type |
IP20 |
Article Number/Certification |
|
Article number |
20-017-441 |
Standardization/certification |
UL 508 (E247993) |