For the S-DIAS system, EPLAN Macros are available for simple integration into the control cabinet.
Performance Data |
|
Voltage monitor |
Yes |
Analog Outputs |
|
Type |
Current |
Number |
4 |
Output range |
-10.8 V ... +10.8 V / 0 V ... +10.8 V or 0 mA ... 21.6 mA / 3.8 mA ... 21.6 mA |
Resolution |
16 bits |
Refresh time for all channels |
minimum 100 µs (corresponds to the S-DIAS cycle time) |
Output voltage capacity |
maximum 2 mA |
Settling time |
200 µs typical for C < 100 nF (99.9 % of the end value) |
Accuracy |
±0.4 % or ±0.17 % of maximum output value |
Galvanic isolation |
Yes |
Mechanical Features |
|
Dimensions |
12.5 x 104 x 72 mm (W x H x D) |
Protection type |
IP20 |
Article Number/Certification |
|
Article number |
20-010-046 |
Standardization/certification |
UL 508 (E247993) |