For the S-DIAS system, EPLAN Macros are available for simple integration into the control cabinet.
Performance Data |
|
Supply voltage |
+24 V DC (+18-30 V DC) |
IEPE Interfaces |
|
Type |
IEPE interface |
Amount |
4 |
Measurement range |
±0.172 ... ±5.5 V AC |
Resolution |
16 bits |
Conversion rate/channel |
≥ 5 µs (adjustable, default setting 5 µs) |
Data recording/channel |
maximum 64 Word |
Short-circuit proof, current limited |
Yes |
Cable break monitor |
Yes |
Hardware filter |
typically 31 MHz (high pass 1st order), typically 20 kHz (low pass 3rd order) |
Software Band Pass Filter |
|
Lower frequency limit |
adjustable (minimum 0.1 Hz) |
Upper frequency limit |
adjustable (maximum 10 kHz) |
Processed measured values/cycle |
configurable |
Output parameters |
Average Value, Minimum Value, Timestamp, Minimum Value, Timestamp, Maximum Value |
Sensor Supply |
|
Adjustable current |
0, 4, 8, 12 mA individually adjustable for each channel |
Supply voltage |
+18-30 V DC |
Sensor voltage |
typically 19.1 V DC |
Mechanical Features |
|
Dimensions |
12.5 x 104 x 72 mm (W x H x D) |
Protection type |
IP20 |
Article Number/Certification |
|
Article number |
20-009-040 |
Standardization/certification |
UL 508 (E247993) |