For the S-DIAS system, EPLAN Macros are available for simple integration into the control cabinet.
Analog Inputs |
|
Type |
±10 V DC resp. potentiometer 0-100 % |
Number |
6 |
Resolution |
16 bits |
Measurement range |
-10 V ... +10 V or 0-100 % (potentiometer) |
Measurement precision |
±0.3 % of maximum measurement value or ±0.35 % of the maximum value |
Conversion time per channel |
standard mode: 250 µs |
Cable break monitor |
Yes |
Hardware filter |
typically 1 kHz, low pass 3rd order |
Software filter |
configurable |
Analog Inputs |
|
Type |
temperature |
Number |
1 |
Resolution |
0.1 °C |
Sensor types |
PT1000 KTY10 |
Measurement range |
-125 ... +850 °C or 500.6-4575.3 Ω |
Measurement precision |
±0.5 % of maximum measurement value |
Conversion time per channel |
standard mode: 250 µs |
Cable break monitor |
Yes |
Hardware filter |
typically 1 kHz, low pass 3rd order |
Software filter |
10 Hz |
Reference Output |
|
Number |
1 |
Reference voltage |
+10 V DC |
Allowable output current |
maximum 25 mA (≥ HW version 1.5, TaMAX = 55 °C) |
Short-circuit proof, current limited |
Yes |
Accuracy |
±0.5 % |
Mechanical Features |
|
Dimensions |
12.5 x 104 x 72 mm (W x H x D) |
Protection type |
IP20 |
Article Number/Certification |
|
Article number |
20-009-075 |
Standardization/certification |
UL 508 (E247993) |