Analog Input

AI 022-1

Analog Input

  • 2 analog strain gauge inputs (24 bits)
  • For evaluating measuring bridges (e.g. strain gauge load cells)

 

For the S-DIAS system, EPLAN Macros are available for simple integration into the control cabinet.

Analog Inputs

Type

strain gauge

Number

2

Resolution

24 bits

Measurement range

±1,25 mV ... ±80 mV

Measurement precision

±0.0031 % noise with filter word 2

±0.001 % / °C temperature drift

Sensor break detection

Yes

Bridge supply voltage

+5 V DC

Load cell rated values

0.25-16 mV/V

Maximum load/channel

60-5000 Ω

Mechanical Features

Dimensions

12.5 x 104 x 72 mm (W x H x D)

Protection type

IP20

Article Number/Certification

Article number

20-009-022-1

Standardization/­certification

UL 508 (E247993)

pdf | 138 KB
Product sheet AI 022-1
pdf | 944 KB
Documentation AI 022-1
zip | 1.9 MB
STEP File AI 022-1