For the S-DIAS system, EPLAN Macros are available for simple integration into the control cabinet.
Digital Inputs |
|
Type |
Latch/Digital Input |
Number |
2 |
Input voltage |
+24 V DC (+18-30 V DC) |
Input current |
3.7 mA at +24 V DC |
Input delay |
typically 10 µs |
Digital Inputs |
|
Type |
Enable |
Number |
2 |
Input voltage |
+24 V DC |
Input current |
3 mA at +24 V |
Input delay |
typically 0.5 ms |
Incremental Encoder Input |
|
Number |
1 |
Input signals |
Incremental encoder signal RS422 (A, /A, B, /B, R, /R) RS422 signal (150 Ω termination) Incremental encoder signal TTL (A, B, R) TTL signal (1200 Ω Pull-Up) |
Input frequency |
maximum 125 kHz |
Counter frequency |
maximum 500 kHz |
Resolution |
16 bits |
Signal analysis |
4-port |
Power supply |
+5 V DC/0.2 A short-circuit proof |
Motor Output |
|
Number |
1 |
Supply voltage |
+18-55 V DC |
Current |
maximum 6 A (load-dependent) |
Output voltage |
depending on the supply (+18-55 V DC) |
Output current |
maximum 5 A RMS |
Step resolution |
full step, half step, 4-/8-/16-/32-/64x micro step |
Voltage measurement |
+15-70 V DC |
Temperature measurement |
0-125 °C |
Regen Resistor |
|
Output |
GND-switching |
Max. Current |
6 A |
Mechanical Features |
|
Dimensions |
25 x 103.5 x 72 mm (W x H x D) |
Protection type |
IP20 |
Article Number/Certification |
|
Article number |
20-014-151 |
Standardization/certification |
UL 61800-5-1 (E336350) |